Facilities Technologies
Testing liquid-handling system components to ensure purity and reliability
Donald C. Grant, Dennis Chilcote, Wayne Kelly, and Mark R. Litchy,
CT Associates; and Allen Rodemeyer, Dave Henderson, and Kenji
Kingsford, Saint-Gobain Performance Plastics
While awaiting industrywide specifications, a component supplier
has adopted a three-pronged test program.
Because the processes used to produce state-of-the-art microcircuits
are extremely sensitive to contamination, the cleanliness of the systems
that supply process chemicals and other fluids is a critical concern
to semiconductor manufacturers. Contaminants from equipment subsystems
and components can and do lead to process defects and lower-yielding
wafers. For example, particulate contamination can cause open or short
circuits, structural defects, altered electrical properties, and unreliable
photolithographic reproduction. Metallic contaminants on the wafer surface
can diffuse into the substrate during subsequent heat treatments, causing
drifts in surface potential, current leakage, structural defects in
vapor-grown epitaxial layers, and reduced breakdown voltage of gate
oxides.
While the need for ultraclean equipment has long been clear, cleanliness
guidelines for the manufacturers who produce such systems have been
slow in coming. SEMI has recently released specifications for particulate
and metallic contamination in components.1 Not included,
however, are specifications for particle release, while requirements
for metallic extractables are based on extraction into water. Section
3.7 states that the relative leach-out performance of polymer components
in actual use with other chemicals (e.g., acids and bases) cannot be
directly derived by using the ultrapure water (UPW) data. Hence, companies
must set their own specifications for their products and components
used to transport process chemicals. The chemical-management division
of BOC Edwards (Santa Clara, CA), for example, has adopted specifications
for particle release and metal extraction from the components used in
its chemical delivery systems.
 |
| Figure 1: Particle addition by a variety of fluid-handling
components under steady-flow conditions.7 |
Another major concern for semiconductor manufacturers is component
reliability, since equipment failures result in costly fab downtime.
Often a component's resistance to damage is dependent on the chemical
it contacts. For example, diaphragm valves have two main modes of failure.
Internal metal components such as springs usually fail because of metal
corrosion caused by exposure to acids that permeate the diaphragm. Hydrochloric
acid (HCl) is thought to be the greatest contributor to this type of
failure. The other major failure mode is diaphragm fatigue, possibly
exacerbated by environmental stress cracking (ESC). In ESC, crack propagation
through plastics subjected to stress is accelerated by a weak plastic-chemical
interaction. Hydrofluoric acid (HF) is believed to be the chemical most
responsible for fatigue failure of fluoropolymer diaphragms.
In response to these industry concerns, component supplier Saint-Gobain
Performance Plastics (Garden Grove, CA) has adopted a testing program
for its components used in high-purity semiconductor applications. This
article describes the testing program that was conducted by CT Associates
(Bloomington, MN), the program's goals, the experimental and analytical
procedures used, and examples of the test results.
A component-testing program offers several benefits. Because it measures
and verifies component performance, it increases customer confidence
in the company's products. In addition, it enables the component manufacturer
to make informed decisions about process changes. For example, new materials
or cleaning processes can be evaluated to ensure that they maintain
or improve component quality.
The program adopted by Saint-Gobain includes separate protocols for
particle release, metal extraction, and reliability. The component cleanliness
goals are based on the specifications set by BOC Edwards. These specifications
mandate that components must release <2 >0.1-µm particles/ml/m2
within 1000 L of flushing. Active componentsthat is, those with
moving partsare exempt from this requirement if they add <0.1
>0.1-µm particles/ml to water flowing through the component within
300 L of flushing. However, active components must meet a second specification
limiting particle release during operation. For example, valves must
release <100 >0.1-µm particles per actuation cycle within 500
cycles. The test program measures particle shedding by monitoring particle
release into flowing UPW. Active components, such as valves and pumps,
are also tested for particle release into UPW during operation.
The BOC Edwards specifications also stipulate that its systems must
not contribute more than 20% of the metallic contaminant concentrations
allowed by the Semiconductor Industry Association roadmap for process
chemicals.2 System specifications are normalized for surface
area so that the contamination limit for individual components can be
calculated.3 The respective component-purity specifications
for surface contamination and bulk extraction rate are £20 ng/cm2
and £0.5 ng/cm2/day after 7 days of chemical exposure. The
company also requires that component testing be performed in 3537%
HCl, 49% HF, or 70% nitric acid because these chemicals aggressively
extract metals present in the polymers.4
The test program under discussion uses BOC Edwards' DyconEX
dynamic extraction procedure to determine the rate of metal extraction
over time.5 (Theory predicts, and test results have demonstrated,
that the rate of metal extraction from components decreases over time.)
The extraction tests are performed in HCl because it is one of the most
effective acids for extracting metals from fluorinated polymers.4
The dynamic extraction procedure has several advantages over techniques
in which metal concentrations in an extractant are measured at the end
of a static soak period. Unlike those conventional methods, dynamic
extraction can measure and predict any change in extraction rate. Its
use of a small chemical volume and multiple sample points over time
also makes the method sensitive enough to detect very low levels of
extractables. Results can be used to predict a component's contribution
to contamination in a process chemical stream.6 Finally,
the technique can be used to distinguish between surface and bulk contamination,
which enables engineers to understand how a component will affect a
system at start-up and over time.
The program's third protocol addresses component reliability under
operating conditions. Active components, such as valves and pumps, are
evaluated in both 37% HCl and 49% HF, ensuring that their potential
for failure via different mechanisms will be detected. The tests are
continued until 70% or more of the test components have failed, which
provides an adequate basis for statistical analysis.
Experimental and Analytical Procedures
Particle Release Testing. Component cleanliness is tested by
measuring particles shed into UPW, which meets the following specifications:
>18 MW/cm resistivity, <5 ppb total
organic carbon, and <0.1 >0.1-µm particles/ml. Both
active and passive components, such as tubing and tanks, are evaluated
for passive shedding under steady-flow conditions, and active components
are also tested under operating conditions, which can generate particle
excursions. For example, valve actuation can cause a burst of particles
to be released into the fluid stream.
Before the program began, the steady-flow test for particle shedding
had been used with many types of components from different manufacturers.
That work revealed that in tests run at face velocities ranging in Reynolds
number from 100 to 30,000, shedding is independent of velocity and linear
on a log-log plot when plotted as the concentration of particles added
versus flush volume (see Figure 1).7
 |
| Figure 2: Schematic of a typical test system used to measure
passive and active particle shedding from components. |
A typical system used to measure particle shedding is shown schematically
in Figure 2. After entering the system, UPW flows through the component(s)
to be tested at a flow rate calculated to yield a Reynolds number of
approximately 1000. The pressure of the UPW is regulated by a bypass
flowmeter and measured both upstream and downstream of the test equipment.
A portion of the downstream UPW then flows through an optical particle
counter (an HSLIS M50 from Particle Measuring Systems of Boulder, CO,
in this example), which measures the concentrations of >0.05-µm
particles in a steady 100-ml/min flow stream. Valves can also be tested
under operating conditions in this apparatus. In such tests, the valves
are actuated in a repeating sequence with compressed dry air (CDA) using
a programmable logic controller.
Prior to each test, the background particle concentrations of the system
are measured using a spool piece in place of the test components. For
steady-flow, passive particle-shedding tests, a single component is
then installed in the system and flushed with UPW as described above,
either until background particle concentrations are achieved or until
the flush volume reaches 1000 L. Concentration data from two to four
parts of each type are averaged to determine component cleanliness.
To measure active shedding, two valves are installed in parallel and
cycled two times per minute using an alternating pattern of 16 seconds
open and 14 seconds closed. Because one of the valves is always open,
this pattern minimizes system hydraulic shocks and ensures a constant
pressure and flow rate at the particle counter. The valves are cycled
through the open/close cycle a minimum of 2000 times.
 |
| Figure 3: Particle shedding from one type of valve under steady-flow
conditions. |
For the steady-flow tests, particle shedding from each component is
calculated by subtracting the system background from each sample's concentration.
The data are then plotted versus flush volume, as shown in the example
in Figure 3. In this case, particle addition decreased linearly with
flush volume on a log-log scale, as expected. The asterisk in the figure
represents the goal for particle release from active components of <0.1
>0.1-µm particles/ml added within 300 L of flushing. The regression
line for the data must fall below the asterisk for the goal to be achieved,
which it does in this example.
For the cycling tests, the number of particles released per valve cycle
is plotted versus total valve cycles, as shown in Figure 4. The goal
of <100 >0.1-µm particles added per cycle within the first 500
cycles is represented by the asterisk. In this example, two types of
test valves surpassed this goal: particle release fell below 100 particles
per cycle in just 280 and 30 cycles, respectively.
 |
| Figure 4: Particles released from two types of valves during
cycling. |
Metallic Extraction Testing. In any test for metallic contaminants
from components, it is important to distinguish between surface and
bulk contamination. Failure to do so can lead to incorrect conclusions
about the cleanliness of a component or the efficacy of a cleaning process.
Surface contamination in this context has been defined as the
mass of contaminants removed from the component within 40 minutes of
exposure to the extracting chemical. Any subsequent contaminant removal
is considered extraction from the bulk of the component material. Bulk
contaminants must be quantitated because they can continue to leach
from components during microcircuit production.
The DyconEX dynamic extraction system used in the test program
to determine both surface contamination and bulk extraction is shown
in Figure 5. All of the system's wetted components are made of fluoropolymers.
Located in a Class 100 cleanroom, the system has been preconditioned
in concentrated (35 to 37%) HCl to eliminate its potential contribution
to measurable metal extraction. The number of test components plumbed
into the apparatus for each test run depends on the components' internal
surface area. Enough parts are included to ensure a minimum of 300 cm2
of wetted surface area. Trace-metal-quality, concentrated HCl is used
as the extractant.
 |
Figure 5: Schematic of a test system used to measure metal
extraction from components.
|
To maximize the sensitivity of the test, the amount of chemical used
is limited to that needed to fill the system plumbing and test components
and permit the drawing of 750 ml of chemical samples. Approximately
1 L of HCl is usually required. The chemical flow through the test component(s)
is maintained at 300 ml/min throughout most tests, although higher flow
rates are used for large components.
Just prior to initiating chemical circulation, the system is charged
with the extractant and a background sample is taken from a sampling
port located in the bypass loop. Then, during the test run, extractant
samples are taken at approximately evenly spaced time intervals on a
log scale. These samples are analyzed for a group of 20 trace metals
using inductively coupled plasmamass spectroscopy and graphite
furnace atomic absorption spectroscopy. The results of the analyses
are converted to cumulative mass extracted and normalized for the wetted
surface area of each component. The concentration increases attributable
to bulk contamination are calculated by subtracting surface metal concentrations
from subsequent samples. The examples of analytical plots shown in Figure
6 depict results from valves cleaned by a proprietary process. Figure
6a shows the data from the first 3 hours of extraction, and Figure 6b
plots the entire 290-hour extraction period.
 |
| Figure 7: Data from Figure 6 expressed as the masses of metals
extracted from the cleaned valves. |
Figure 7 shows the same data expressed as the mass of metals extracted
per unit area of wetted surface, the values of which are determined
by multiplying the concentration data by the volume of chemical in the
test system and divid- ing that product by the wetted surface area of
the test component. The solid symbols represent surface contamination
while the open symbols represent bulk contamination of the bulk contamination
data. Regression lines of the bulk contamination data have been added
to the plot, revealing that bulk extraction of metals is linear with
time on a log-log scale, as predicted by theory.5 The mass
of metal extracted at different times can be calculated using the following
formula:
where t = time (days), m = normalized cumulative mass
extracted (ng/cm2) at time t, k = a proportionality
constant, and n = an exponent. In addition, the rate of extraction
can be determined using the following derivative of the equation with
respect to time:
Rate of extraction = dm/dt = n x k x tn
1
Based on these equations, the normalized mass extraction rate calculated
from the valve data in the example was 0.49 ng/cm2/day after
7 days, and the total surface contamination for the 20 elements was
16.5 ng/cm2. Thus, these valves met the cleanliness goals
for metal extraction from active components for both surface contamination
(£20 ng/cm2) and bulk extraction (£0.5 ng/cm2/day
after 7 days).
Reliability Testing. The third part of the test program involves
testing valves in both HCl and HF, which are known to contribute to
the most likely failure mechanisms. To have sufficient data for statistical
analysis, at least 10 valves must be evaluated in each test run. Shown
schematically in Figure 8, the test apparatus allows parallel flows
of chemical through all 10 test valves, which are opened and closed
approximately six times per minute with an actuator pressure equal to
the lower of 70 psi or maximum valve rating. The cleanroom-grade chemical
is supplied to the valves from a reservoir using a double-diaphragm
pump and passes through a 0.45-µm filter before entering the valve
manifold. Chemical pressure is maintained at 65 ± 5 psi. To ensure
that full chemical strength is maintained, the reservoir is replenished
every 400,000 cycles.
 |
| Figure 8: Schematic of the system used for reliability testing. |
Valves that leak or show other visible signs of failure during the
test cycling are removed from the apparatus immediately, and valves
that exhibit no visible signs of failure every 200,000 cycles are removed
to undergo cracking-pressure and port-to-port integrity tests. Using
the test stand shown in Figure 9, each valve's cracking pressure is
determined by applying air pressure to the closed valve and measuring
the pressure at which it opens.
 |
| Figure 9: Schematic of the test stand used for measuring cracking
pressure and port-to-port leakage. |
The test is conducted on both the inlet and outlet of the valve, and
the maximum pressure applied is 125 psi. If a valve's measured cracking
pressure is >120% of its rated pressure, the valve is returned to
the test manifold. If its cracking pressure is £120% of its rated pressure,
it is also tested for port-to-port integrity. This test measures the
rise in pressure downstream of the closed valve when its rated pressure
is applied. Valves fail if the pressure rise corresponds to a leak rate
in water of >0.0001 ml/min or >0.14 ml/day. Valves that pass this test
are returned to the test manifold. The open/close cycling then continues
until at least 70% of the valves have failed.
 |
| Figure 10: Results of an analysis of one valve type's reliability
in 49% HF. |
The resulting data are analyzed for median cycles to failure and the
number of cycles at which 5% of the valves have failed. The percent
failure data indicate the valve type's probability of failure. For example,
Figure 10, which is based on a test using 49% HF, plots the probability
that the test valve will fail as a function of millions of open/close
cycles. The reliability testing has revealed that failures are lognormally
distributed (a statistical concept that is explained in detail elsewhere8),
and the figure is based on that assumption. The x-axis is a probability
scale, the y-axis is a log scale, and the solid line represents a fit
of the data to a lognormal distribution. The dashed lines show the number
of cycles that had been completed when 5 and 50% of the valves failed.
Specifically, these lines indicate that there is a 5% probability of
a valve of this type failing in HF before it completes 830,000 cycles,
and a 50% probability of its failure before 2.3 million cycles.
The three test protocols have been used to evaluate a variety of components
including piping, unions, and valves. The results of five particle-shedding
tests are presented in Table I, along with the cleanliness goal for
active components. The 1/2-in.
tubing, the only passive component included in this testing, has a different
goal, as noted in the table. Comparison of the test data with the goals
shows that the tubing met its single goal, and valve A met the goals
for both steady-flow and cycling tests. The other three valves each
met one of the two relevant goals.
|
Component
|
Steady-Flow Tests
(volume in liters to
<0.1>0.1-µm particles/ml added
|
Cycling Tests (cycles to <100>0.1-µm
particles released per cycle)
|
| 1/2-in. tubing |
60
|
NA
|
| Valve A |
250
|
280
|
| Valve B |
940
|
<100
|
| Valve C |
190
|
>2000
|
| Valve D |
850
|
310
|
| Cleanliness goal (a) |
£300
|
£510
|
| (a) The
goal for passive components (tubing, piping, tanks, etc.) is <2>0.1-µm
particles/ml/m2 added within 1000L. |
| Table I: Summary of particle release test data. |
|
Component
|
Mass Extracted (ng/cm2)
|
Extraction Rate
at 7 Days
(ng/cm2/day)
|
|
Surface
|
Bulk
|
Total
|
| 1/2-in. tubing |
0.29
|
0.48
|
0.77
|
0.02
|
| 1/2-in. union |
7.1
|
2.0
|
9.1
|
0.04
|
| Valve A |
3.6
|
3.3
|
6.9
|
0.11
|
| Valve B |
180.0
|
36.0
|
216.0
|
0.61
|
| Valve C |
14.0
|
7.8
|
22.0
|
0.28
|
| Valve D |
19.0
|
26.0
|
45.0
|
0.87
|
| Check valves |
12.0
|
9.5
|
22
|
0.35
|
| Cleanliness goal |
£2.0
|
|
|
£0.50
|
| SEMI specification (a) |
|
|
£12.0
|
|
| (a)
For parts in UPW at 85° ± 5°C. |
| Table II: Summary of metal extraction test data. |
Table II summarizes the results of several metal extraction tests.
The SEMI specification given in the table refers to total metal extraction
under other, presumably less stringent, conditions and is included for
information only. All of the components tested met the cleanliness goals
except valves B and D. Because the type B valves failed to meet both
the metal extraction and the steady-flow particle release test goals,
Saint-Gobain began investigating a new cleaning process that would reduce
contamination levels. In recent testing, valves cleaned with this process
met all cleanliness goals, and the process is now being implemented.
|
Valve Type
|
Test Fluid
|
Statistics of Failure
|
Main
Failure Mode
|
|
Median
(millions of cycles)
|
Geometric
Standard
Deviation
|
| A |
37% HC
|
>1.0 (a)
|
|
|
| B |
37% HCl
|
7.0 (b)
|
|
|
| C |
37% HCl
|
2.90
|
1.14
|
Spring
|
| C |
49% HF
|
2.28
|
1.85
|
Diaphragm
|
| D |
37% HCl
|
1.40
|
1.45
|
Spring
|
(a)
Both 1/4- and 1/2-in valves tested to 1 million cycles with no failures.
(b) Valves cycled 7 million times with no
failures. |
| Table III: Summary of reliability testing data,
expressed as statistics of failure and failure mode. |
|
Valve Type
|
Test Fluid
|
Failure Rate
(millions of cycles to failure)
|
|
5% Failure
|
50% Failure
|
| A (a) |
37% HCl
|
>0.86
|
>1.7
|
| B (a) |
37% HCl
|
>6
|
>11
|
| C (b) |
37% HCl
|
2.3
|
2.9
|
| C |
49% HF
|
0.82
|
2.3
|
| D |
37% HCl
|
0.76
|
1.4
|
(a)
Failure rate was estimated because no failures were observed during
testing. Estimates were made assuming that failures are lognormally
distributed with a geometric standard deviation of 1.5 and that
one of 10 valves failed one cycle after the last test point. The
value of 1.5 assumed for the geometric standard deviation was based
on historical data.
(b)
Failure rate was estimated assuming that a failure at 800,000 cycles
was not representative of the general valve population. |
| Table IV: Summary of reliability testing data,
expressed as valve cycles to a 5 and 50% probability of failure. |
Reliability test results for the four types of valves tested are summarized
in Tables III and IV. As the statistical data in Table III show, type
A valves showed no failures after 1 million cycles, and valves D and
C had median cycles to failure of 1.4 million and approximately 2.5
million cycles, respectively. Although the median cycles to failure
for the type C valves tested in HF and HCl were similar, the failure
modes were different and failure times were more variable in HF. Tests
of the type B valves are continuing, with no failures after 7 million
cycles. Additional testing of type A valves is planned to determine
failure statistics.
Table IV presents reliability data in terms of the number of cycles
run before 5 and 50% of the test valves failed. This method of expressing
the test results is useful in deciding how frequently the various types
of valves should be replaced. All of the valves tested reached the 5%
failure rate after more than 0.7 million cycles, while valve B had a
5% failure rate of >6 million cycles. (It should be noted that some
of the numbers in this table were estimated.)
To protect against wafer defects and low device yields, the components
used in high-purity chemical distribution systems must release very
low levels of contaminants and be highly reliable. Rigorous component
testing for particle release, metal extraction, and reliability can
help ensure that these goals are met. A test program established by
Saint-Gobain Performance Plastics includes particle-shedding tests that
measure particle release in ultrapure water under steady-flow and open/close
cycling conditions, a dynamic test that measures the rate of metal extraction
in concentrated acid over time, and reliability tests in which components
are exposed to 37% HCl or 49% HF under operating conditions. In order
to provide an adequate basis for statistical analysis, the reliability
tests are continued until 70% or more of the components have failed.
The use of these tests has led to both product and manufacturing improvements,
including the development of a cleaning procedure that reduces contamination
in components.
This article is based on a presentation given at the Semiconductor
Pure Water and Chemical Conference (SPWCC) on February 28, 2001, in
Monterey, CA. The presentation appears in the conference proceedings.
Used with permission.
1. "Provisional Specification for Polymer Components Used in Ultrapure
Water and Liquid Chemical Distribution Systems," SEMI F57-1000 (San
Jose: SEMI, 2000).
2. International Technology Roadmap for Semiconductors (San
Jose: SIA, 2000), 13.
3. D Carrieri, T Lemke, and DC Grant, "Specification and Verification
of Metallic Extractables in Fluid Handling Components," in Proceedings
of the Semicon West Workshop on Contamination in Liquid Chemical Distribution
Systems (Mountain View, CA: SEMI, July 1997), C1C8.
4. D Chilcote et al., "The Extraction of Surface and Bulk Trace Metal
Impurities from Typical Fluoropolymers," in Proceedings of the Semicon
West Workshop on Contamination in Liquid Chemical Distribution Systems
(Mountain View, CA: SEMI, July 1998), C1C10.
5. DC Grant et al., "Measurement of Inorganic Contaminant Extraction
from Fluid-Handling Components by Dynamic Extraction," Journal of
the Institute of Environmental Sciences 39, no. 2 (1996): 2937.
6. T Lemke and DC Grant, "Dynamic Extraction: A New Technique for Measuring
Metallic Extractables from Chemical Delivery Systems," in Proceedings
of the 13th Annual Technical Symposium: Partnering for Contamination-Free
Manufacturing (Bedford, MA: Millipore, 1995).
7. W Kelly et al., "The Effect of Fluid Dynamics on Particle Shedding
from Semiconductor Fluid-Handling Components," in Particles on Surfaces
5 & 6: Detection and Removal, ed. K Mittal (Utrecht, The Netherlands:
VSP, 1999), 4758.
8. WC Hinds, Aerosol Technology (New York: Wiley, 1982), 8395.
Donald C. Grant is president of CT Associates (Bloomington,
MN), which performs contract R&D in contamination control, particle
measurement and control, filtration, and chemical engineering. He has
more than 25 years of experience in the areas of analysis and purification
of fluids, has written or cowritten more than 100 technical papers and
presentations, and is a recipient of the Maurice Simpson Award from
the Institute of Environmental Sciences. Grant received an MS in mechanical
engineering from the Particle Technology Laboratory at the University
of Minnesota (Minneapolis) and a BS in chemical engineering from Case
Western Reserve University (Cleveland). (Grant can be reached at 952/944-4766
or don@ctassociatesinc.com.)
Dennis Chilcote, PhD, is a consulting engineer with CT Associates,
specializing in biotechnology, water treatment, and environmental engineering.
His broad experience in process design has been applied to the leaching
of metals in aqueous solutions, the development of clinical instrumentation,
and the design and fabrication of a variety of water treatment processes.
Chilcote received a PhD in chemical engineering from the California
Institute of Technology (Pasadena, CA), with an emphasis on bioengineering.
He also received a BS in chemical engineering from the University of
Minnesota in Minneapolis. (Chilcote can be reached at 952/944-4764 or
dennis@ctassociatesinc.com.)
Wayne Kelly joined CT Associates in 1994 and focuses on the
areas of liquid filtration and microcontamination. Prior to joining
the company, he worked at TSI in the contamination monitoring instruments
group. Kelly received a BS from the University of Kansas (Lawrence)
and an MS from the University of Minnesota (Minneapolis), both in mechanical
engineering. (Kelly can be reached at 952/944-4765 or wayne@ctassociatesinc.com.)
Mark R. Litchy joined CT Associates as a research engineer in
1996. He has several years of experience in particle measurement and
control in high-purity liquid chemicals and gases, as well as surface
contamination and cleaning. He has an MS in mechanical engineering from
the Particle Technology Laboratory at the University of Minnesota (Minneapolis)
and a BA in physics from St. John's University in St. Cloud, MN. (Litchy
can be reached at 952/944-4773 or mark@ctassociatesinc.com.)
Allen Rodemeyer supervises the research and development laboratory
for the engineered components group at Saint-Gobain Performance Plastics
(Garden Grove, CA). He has been with the firm since 1993 and has more
than 18 years of experience in an R&D environment focusing on destructive,
nondestructive, environmental, and reliability testing. He holds an
AS in electronic technologies from Riverside Community College (Riverside,
CA) and is working toward a BS in mechanical engineering at California
State University, Fullerton. (Rodemeyer can be reached at 714/238-1377
or william.a.rodemeyer@saint-gobain.com.)
Dave Henderson is a market engineer for Saint-Gobain Performance
Plastics. He is an active member of SEMI standards committees and is
an author of three patents, two of which have issued. He has a BS in
electrical engineering from California State Polytechnic University
(Pomona) and 10 years of experience in fluid-handling product design
and semiconductor process applications. (Henderson can be reached at
909/867-5931 or david.l.henderson@saint-gobain.com.)
Kenji Kingsford is director of technology for Saint-Gobain Performance
Plastics. He received a BS in mechanical engineering from California
State University, San Bernardino, and has 17 years of experience in
fluid-handling product design for the semiconductor industry. He holds
17 patents for semiconductor-based products and is also an active member
on SEMI standards committees. (Kingsford can be reached at 714/238-1343
or kenji.a.kingsford@saint-gobain.com.)

MicroHome |
Search | Current Issue | MicroArchives
Buyers Guide | Media Kit
Questions/comments about MICRO Magazine? E-mail us at cheynman@gmail.com.
© 2007 Tom Cheyney
All rights reserved.
|